Monitored Data; Technical Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
Table 761:
PSPTUV Non group settings (Advanced)
Parameter
Reset delay time
Relative hysteresis
4.5.6.9
4.5.6.10
800
Values (Range)
Unit
0...60000
ms
1.0...5.0
%

Monitored data

Table 762:
PSPTUV Monitored data
Name
START_DUR
PSPTUV

Technical data

Table 763:
PSPTUV Technical data
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
Start value = 1.0 × U
1)
undervoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Step
Default
1
20
0.1
4.0
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
U
= 0.99 × set
Start
Fault
value
Start
U
= 0.9 × set
Fault
value
, positive-sequence voltage before fault = 1.1 × U
n
Description
Reset delay time
Relative hysteresis for operation
Unit
Description
%
Ratio of start time /
operate time
Status
Value
Depending on the frequency of the measured
voltage: f
±2 Hz
n
±1.5% of the set value or ±0.002 × U
Minimum
Typical
52 ms
55 ms
44 ms
47 ms
Typically 40 ms
Relative hysteresis
Depends on the set
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
, f
= 50 Hz, positive sequence
n
n
1MRS759142 C
n
Maximum
58 ms
50 ms
REX640
Technical Manual