Technical Data; Transient/Intermittent Earth-Fault Protection Intrptef; Identification - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.2.14
4.2.3
4.2.3.1
444

Technical data

Table 500:
DEFxPDEF Technical data
Characteristic
Operation accuracy
DEFLPDEF
DEFHPDEF
1)2)
Start time
DEFHPDEF
I
Fault
value
DEFLPDEF
I
Fault
value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Measurement mode = default (depends on stage), current before fault = 0.0 × I
1)
current with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value = 2.5 × I

Transient/intermittent earth-fault protection INTRPTEF

Identification

Function description
Transient/intermittent earth-fault
protection
Value
Depending on the frequency of the measured
current: f
Current:
±1.5% of the set value or ±0.002 × I
Voltage
±1.5% of the set value or ±0.002 × U
Phase angle:
±2°
Current:
±1.5% of the set value or ±0.002 × I
(at currents in the range of 0.1...10 × I
±5.0% of the set value
(at currents in the range of 10...40 × I
Voltage:
±1.5% of the set value or ±0.002 × U
Phase angle:
±2°
Minimum
= 2 × set
Start
42 ms
58 ms
Start
= 2 × set
Typically 40 ms
Typically 0.96
<30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n × f
Peak-to-Peak: No suppression
,
Start value multiples in range of 1.5...20
n
IEC 61850
identification
INTRPTEF
1MRS759142 C
±2 Hz
n
n
n
n
n
n
Typical
Maximum
46 ms
49 ms
62 ms
66 ms
, where n = 2, 3, 4, 5,...
n
, f
= 50 Hz, earth-fault
n
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
Io> -> IEF
67NTEF/NIEF
Technical Manual
)
n
)
3)
REX640