1MRS759142 C
REX640
Technical Manual
s2
GUID-5E9C7D3D-656B-4736-BCFE-F4AD96F2B805 V1 EN
Figure 374:
Connection scheme for the restricted earth-fault protection according
to the high-impedance principle
High-impedance principle
High-impedance principle is stable for all types of faults outside the zone of
protection. The stabilization is obtained by a stabilizing resistor in the differential
circuit. This method requires that all the CTs used have a similar magnetizing
characteristic, same ratio and relatively high knee point voltage. CTs on each sides are
connected in parallel along with a relay-measuring branch as shown in
The measuring branch is a series connection of stabilizing resistor and protection
relay.
s1
VDR
Stabilizing
Resistor
High impedance
protection
(HREFPDIF)
Section 4
Protection functions
s1
s2
Figure
375.
675