ID> BLOCKED
BLKD2H_LOC
GUID-FAED35DA-C75A-4FA2-9583-03457CFE0D0A V1 EN
Figure 326:
Blocking of line differential functions during detected transformer
startup current
If the protection stage is allowed to start during the inrush situation, the time delay can
be selected so that the stabilized stage does not operate in the inrush situation.

Signals

Table 573:
LNPLDF Input signals
Name
Type
I3P
SIGNAL
BLOCK
BOOLEAN
BLOCK_LS
BOOLEAN
ENA_MULT_HS
BOOLEAN
RED 615
INRUSH
Default
Description
-
Three-phase currents
0=False
Signal for blocking the function
0=False
Signal for blocking the stab. stage
0=False
Enables the high stage multiplier
Section 4
Protection functions
ID> BLOCKED