Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.1.2.11
REX640
Technical Manual

Monitored data

Table 385:
DPHLPDOC Monitored data
Name
Type
START_DUR
FLOAT32
DIR_A
Enum
DIR_B
Enum
DIR_C
Enum
ANGLE_A
FLOAT32
ANGLE_B
FLOAT32
ANGLE_C
FLOAT32
VMEM_USED
BOOLEAN
DPHLPDOC
Enum
Table 386:
DPHHPDOC Monitored data
Name
Type
START_DUR
FLOAT32
DIR_A
Enum
DIR_B
Enum
DIR_C
Enum
ANGLE_A
FLOAT32
ANGLE_B
FLOAT32
Table continues on next page
Protection functions
Values (Range)
Unit
0.00...100.00
%
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
-180.00...180.00
deg
-180.00...180.00
deg
-180.00...180.00
deg
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
Values (Range)
Unit
0.00...100.00
%
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
-180.00...180.00
deg
-180.00...180.00
deg
Section 4
Description
Ratio of start time /
operate time
Direction phase A
Direction phase B
Direction phase C
Calculated angle
difference, Phase A
Calculated angle
difference, Phase B
Calculated angle
difference, Phase C
Voltage memory in use
status
Status
Description
Ratio of start time /
operate time
Direction phase A
Direction phase B
Direction phase C
Calculated angle
difference, Phase A
Calculated angle
difference, Phase B
347

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents