ABB RELION REX640 Technical Manual page 329

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 354:
PHHPTOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
Table 355:
PHHPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Num of start phases
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Table 356:
PHHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Measurement mode
Table 357:
PHIPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Operate delay time
Table 358:
PHIPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Num of start phases
REX640
Technical Manual
Unit
1=Immediate
2=Def time reset
3=Inverse reset
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
Unit
0.10...40.00
xIn
0.8...10.0
20...300000
ms
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
Step
Default
1=Immediate
Step
Default
1=on
1=1 out of 3
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Step
Default
1
20
1
20
2=DFT
Step
Default
0.01
1.00
0.1
1.0
10
20
Step
Default
1=on
1=1 out of 3
Section 4
Protection functions
Description
Selection of reset curve type
Description
Operation Off / On
Number of phases required for operate
activation
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Description
Start value
Multiplier for scaling the start value
Operate delay time
Description
Operation Off / On
Number of phases required for operate
activation
323

Hide quick links: