1MRS759142 C
4.7.4.7
4.7.4.8
Table 882:
UZPDIS Group settings (Basic)
Parameter
Values (Range)
Polar reach
Operate delay time
Table 883:
UZPDIS Non group settings (Basic)
Parameter
Values (Range)
Operation
Measurement mode
Impedance Meas mode
Phase Sel for Z Clc
Table 884:
UZPDIS Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
REX640
Technical Manual
calculated impedance could fall below the set operating limit even if there is no actual
fault in the primary system.
The blocking operation is provided by an external function block, the fuse failure
supervision SEQSPVC, whose output is connected to the BLOCK input of UZPDIS.

Signals

Table 880:
UZPDIS Input signals
Name
I3P
U3P
BLOCK
Table 881:
UZPDIS Output signals
Name
OPERATE
START
Settings
Unit
1...6000
%Zn
40...200000
ms
Unit
1=on
5=off
2=DFT
3=Peak-to-Peak
2=1Phase-to-
phase
4=3Phase-to-
phase
1=AB
2=BC
3=CA
Unit
0...60000
ms
Type
Default
Description
SIGNAL
-
Three-phase currents
SIGNAL
-
Three-phase voltages
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
1
7
10
200
Step
Default
1=on
2=DFT
4=3Phase-to-
phase
1=AB
Step
Default
10
20
Section 4
Protection functions
Description
Impedance start value, i.e. radius of
impedance circle
Operate delay time
Description
Operation Off / On
Selects used measurement mode
Select voltage and current signals for
impedance calculation
Select phase/ phase-phase voltages and
currents for Z calculation.
Description
Reset delay time
951