Section 4
Protection functions
4.1.8.8
Table 435:
PHPTUC Group settings (Basic)
Parameter
Current block value
Start value
Operate delay time
Table 436:
PHPTUC Non group settings (Basic)
Parameter
Operation
Operation mode
Table 437:
PHPTUC Non group settings (Advanced)
Parameter
Reset delay time
4.1.8.9
386
Table 434:
PHPTUC Output signals
Name
OPERATE
OPR_A
OPR_B
OPR_C
START
ST_A
ST_B
ST_C

Settings

Values (Range)
Unit
0.00...0.50
xIn
0.01...1.00
xIn
50...200000
ms
Values (Range)
Unit
1=on
5=off
1=Three Phase
2=Single Phase
Values (Range)
Unit
0...60000
ms

Monitored data

Table 438:
PHPTUC Monitored data
Name
START_DUR
PHPTUC
Type
Description
BOOLEAN
Operate
BOOLEAN
Operate phase A
BOOLEAN
Operate phase B
BOOLEAN
Operate phase C
BOOLEAN
Start
BOOLEAN
Start phase A
BOOLEAN
Start phase B
BOOLEAN
Start phase C
Step
Default
0.01
0.10
0.01
0.50
10
2000
Step
Default
1=on
1=Three Phase
Step
Default
1
20
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS759142 C
Description
Low current setting to block internally
Current setting to start
Operate delay time
Description
Operation Off / On
Number of phases needed to start
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time
Status
Technical Manual
REX640