Section 4
Protection functions
4.1.6.5
376
Table 417:
Analog signals
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of JAMPTOC can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
I_A
I_B
Level
I3P
detector 1
I_C
Blocking
BLOCK
logic
GUID-D3FC1D45-197B-4002-8FFB-C9F0194AEC8F V1 EN
Figure 207:
Functional module diagram
Level detector
The measured phase currents are compared to the set Start value. The TRMS values
of the phase currents are considered for the level detection. The timer module is
enabled if at least two of the measured phase currents exceed the set Start value.
Timer
Once activated, the internal START signal is activated. The value is available only
through the Monitored data view. The time characteristic is according to DT. When
the operation timer has reached the Operate delay time value, the OPERATE output is
activated.
When the timer has elapsed but the motor stall condition still exists, the OPERATE
output remains active until the phase currents values drop below the Start value, that
is, until the stall condition persists. If the drop-off situation occurs while the operating
Description
Three-phase currents
Timer
OPERATE
t
START
1MRS759142 C
REX640
Technical Manual