Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
5.3.6
REX640
Technical Manual
The inputs from the protection functions are connected to the OPERATE input.
Usually, a logic block OR is required to combine the different function outputs to this
input. The TRIP output is connected to the binary outputs on the IO board. This signal
can also be used for other purposes within the protection relay, for example when
starting the breaker failure protection.
TRPPTRC is used for simple three-phase tripping applications.
PHLPTOC-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC-operate
NSPTOC1-operate
NSPTOC2-operate
EFLPTOC1-operate
EFHPTOC-operate
EFIPTOC-operate
EFLPTOC2-operate
PDNSPTOC-operate
T1PTTR-operate
CCRBRF-trret
CBXCBR-open
ARCPSARC1-operate
ARCPSARC2-operate
ARCPSARC3-operate
DARREC-open cb
BI#2
GUID-082A0463-EDBD-432F-81F9-FC79E70456DD V1 EN
Figure 581:
Typical TRPPTRC connection

Signals

Table 1018:
TRPPTRC Input signals
Name
Type
BLOCK
BOOLEAN
OPERATE
BOOLEAN
RST_LKOUT
BOOLEAN
Table 1019:
TRPPTRC Output signals
Name
Type
TRIP
BOOLEAN
CL_LKOUT
BOOLEAN
Protection related functions
OR
BI#4
Lock-out
reset
Default
Description
0=False
Block of function
0=False
Operate
0=False
Input for resetting the circuit breaker lockout
function
Description
General trip output signal
Circuit breaker lockout output (set until reset)
Section 5
TRPPTRC
OPERATE
TRIP
BLOCK
CL_LKOUT
RST_LKOUT
PO#1
1081