Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.2.2.12
Table 490:
DEFLPDEF Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Directional mode
Time multiplier
Table continues on next page
REX640
Technical Manual
Table 487:
DEFHPDEF Input signals
Name
I3P
IRES
U3P
URES
BLOCK
ENA_MULT
RCA_CTL
Table 488:
DEFLPDEF Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION
Table 489:
DEFHPDEF Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION

Settings

Unit
0.010...5.000
xIn
0.8...10.0
1=Non-directional
2=Forward
3=Reverse
0.025...15.000
Type
Default
Description
SIGNAL
-
Three-phase currents
SIGNAL
-
Residual current
SIGNAL
-
Three-phase voltages
SIGNAL
-
Residual voltage
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Enable signal for current multiplier
BOOLEAN
0=False
Relay characteristic angle control
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Enum
Detected fault direction
Enum
Direction information
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Enum
Detected fault direction
Enum
Direction information
Step
Default
0.005
0.010
0.1
1.0
2=Forward
0.005
1.000
Section 4
Protection functions
Description
Start value
Multiplier for scaling the start value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
439

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents