Monitored data

Table 527:
MREFPTOC Monitored data
Name
Type
START_DUR
FLOAT32
MREFPTOC
Enum

Technical data

Table 528:
MREFPTOC Technical data
Characteristic
Operation accuracy
1)2)
Start time
I
Fault
value
Reset time
Reset ratio
Retardation time
Operate time accuracy
Suppression of harmonics
1) Current before fault = 0.0 × I
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

Harmonics-based earth-fault protection HAEFPTOC

Identification

Description
Harmonics-based earth-fault protection
Values (Range)
Unit
0.00...100.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the current
measured: f
±1.5% of the set value or ±0.002 × I
Minimum
Start
= 1.2 × set
30 ms
<50 ms
Typically 0.96
<50 ms
±1.0% of the set value of ±20 ms
-50 dB at f = n × f
, f
= 50 Hz, earth-fault current with nominal frequency injected from
n
n
IEC 61850
identification
HAEFPTOC
Section 4
Protection functions
Description
%
Ratio of start time /
operate time
Status
±2 Hz
n
n
Typical
Maximum
34 ms
38 ms
, where n = 2, 3, 4, 5,...
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
Io>HA