Section 4
Protection functions
4.2.5.7
4.2.5.8
Table 524:
MREFPTOC Group settings (Basic)
Parameter
Operate start value
Alarm start value
Operate delay time
Alarm delay time
Table 525:
MREFPTOC Non group settings (Basic)
Parameter
Operation
Table 526:
MREFPTOC Non group settings (Advanced)
Parameter
Reset delay time
Alm reset delay time
486

Signals

Table 522:
MREFPTOC Input signals
Name
IRES
BLOCK
Table 523:
MREFPTOC Output signals
Name
OPERATE
START
ALARM

Settings

Values (Range)
Unit
0.010...2.000
xIn
0.010...2.000
xIn
40...20000
ms
40...200000
ms
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
0...60000
ms
0...60000
ms
Type
Default
Description
SIGNAL
-
Residual current
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
Alarm
Step
Default
0.001
0.010
0.001
0.010
1
500
1
10000
Step
Default
1=on
Step
Default
1
20
1
20
1MRS759142 C
Description
Operate start value
Alarm start value
Operate delay time
Alarm delay time
Description
Operation Off / On
Description
Reset delay time
Alarm reset delay time
Technical Manual
REX640