Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.20.15.4
250

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off". When the Operation setting is
changed from "off" to "on", the monitored variable TAG_SOURCE is set to "None"
and saved to a nonvolatile memory.
When the Operation setting is "on" and a reboot occurs, the TAG_SOURCE variable
is read from the nonvolatile memory.
The operation of HLTGAPC can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
TAG_ON_OFF
Local
Local
command
Remote
Remote
command
Remote tag mode
GUID-E3CC15C9-6507-4942-8DFF-E7B0547D9EE7 V1 EN
Figure 130:
Functional module diagram
Local tag
Local tag is activated or deactivated on rising edge detection of TAG_ON_OFF input
or with a local command from the LHMI when the protection relay is in local mode.
If a rising edge tag is detected locally, and the status of the nonvolatile variable
TAG_SOURCE is "None", the tag is locally activated. TAG_SOURCE changes to
"Local" while TAG_ON is set to TRUE and TAG_OFF to FALSE.
If a rising edge tag is detected locally, and the status of TAG_SOURCE is "Local", the
tag is locally deactivated. TAG_SOURCE changes to "None" while TAG_ON is set to
FALSE and TAG_OFF to TRUE.
When TAG_SOURCE is "Remote" and the Remote tag mode setting is "Untag Rem
only", all local commands are prohibited. However, when the Remote tag mode
setting is "Untag Loc or Rem", deactivation can be done locally.
Remote tag
Remote tag is activated or deactivated on rising edge detection through a
communication channel in remote mode.
tag
Active
tag
TAG_SOURCE
tag
1MRS759142 C
TAG_ON
TAG_OFF
Technical Manual
REX640