Technical Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.12.1.10
4.12.2
4.12.2.1
4.12.2.2
4.12.2.3
1020

Technical data

Table 959:
COLPTOC Technical data
Characteristic
Operation accuracy
Start time for overload stage
Start time for under current stage
Reset time for overload and alarm stage
Reset ratio
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics for under current stage
1) Harmonics current before fault = 0.5 × I
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Harmonics current before fault = 1.2 × I
statistical distribution of 1000 measurements
Current unbalance protection for shunt capacitor banks
CUBPTOC
Identification
Table 960:
Function identification
Function description
Current unbalance protection for shunt
capacitor banks
Function block
GUID-06102D1C-9021-4641-B061-EE4D064E76AE V1 EN
Figure 551:
Function block symbol
Functionality
The current unbalance protection for shunt capacitor banks function CUBPTOC is
used to protect the double-Y-connected capacitor banks from internal faults.
Value
Depending on the frequency of the measured
current: f
5% of the set value or 0.002 × I
Typically 75 ms
1)2)
Typically 26 ms
2)3)
Typically 60 ms
Typically 0.96
1% of the set value or ±20 ms
10% of the theoretical value or ±20 ms
DFT: -50 dB at f = n × f
, harmonics fault current 1.5 ×
n
, harmonics fault current 0.8 ×
n
IEC 61850
identification
CUBPTOC
1MRS759142 C
±2 Hz, and no harmonics
n
n
, where n = 2,3,4,5,..
n
Start value , results based on
Start value , results based on
IEC 60617
ANSI/IEEE C37.2
identification
device number
dI>C
60N
Technical Manual
REX640