Section 4
Protection functions
4.2.9.7
552
MFADPSDE supports fault direction indication in operate and non-operate directions
which can be used during fault location process. The in-built transient detector can be
used to identify restriking or intermittent earth faults, and discriminate them from
permanent or continuous earth faults.
The direction of MFADPSDE can be set as forward or reverse. The operation
characteristic is defined by a tilted operation sector, which is universally valid both in
unearthed and compensated networks. The tilt of the operation sector should be
selected based on the measurement errors of the applied residual current and voltage
measurement transformers.
The operating time characteristic is according to the definite time (DT).
The function contains a blocking functionality to block function outputs, timers or the
function itself.
MFADPSDE supports both tripping and alarming operation modes. For the alarming
earth-fault protection application, the function contains a dedicated operation mode.
MFADPSDE provides reliability and sensitivity of protection with a single function.
This enables a protection scheme implementation that is simpler than separate fault
type dedicated earth-fault functions which need to be coordinated. Other advantages
of MFADPSDE include versatile applicability, good selectivity, good sensitivity and
easy setting principles.
Three instances (stages) of MFADPSDE are available.

Signals

Table 563:
MFADPSDE Input signals
Name
Type
IRES
SIGNAL
URES
SIGNAL
BLOCK
BOOLEAN
RELEASE
BOOLEAN
RESET
BOOLEAN
Table 564:
MFADPSDE Output signals
Name
Type
OPERATE
BOOLEAN
START
BOOLEAN
BLK_EF
BOOLEAN
INTR_EF
BOOLEAN
PEAK_IND
BOOLEAN
FAULT_DIR
Enum
DIRECTION
Enum
Default
Description
-
Residual current
-
Residual voltage
0=False
Block signal for activating the blocking mode
0=False
External trigger to release neutral admittance
protection
0=False
External trigger to reset direction calculatio
Description
Operate
Start
Block signal for EF to indicate opposite direction
peaks
Intermittent earth-fault indication
Current transient detection indication
Detected fault direction
Direction information
1MRS759142 C
REX640
Technical Manual