1MRS759142 C
4.6.1.5
REX640
Technical Manual
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of FRPFRQ can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
F
U3P
dF/dt
BLOCK
GUID-67A36E21-2379-4164-9F8F-665BDB0033C5 V1 EN
Figure 455:
Functional module diagram
Freq>/< detection
The frequency detection module includes an overfrequency or underfrequency
detection based on the Operation mode setting.
In the "Freq>" mode, the measured frequency is compared to the set Start value
Freq>. If the measured value exceeds the set value of the Start value Freq> setting,
the module reports the exceeding of the value to the operate logic module.
In the "Freq<" mode, the measured frequency is compared to the set Start value
Freq<. If the measured value is lower than the set value of the Start value Freq<
setting, the module reports the value to the operate logic module.
df/dt detection
The frequency gradient detection module includes a detection for a positive or
negative rate-of-change (gradient) of frequency based on the set Start value df/dt
value. The negative rate-of-change protection is selected when the set value is
negative. The positive rate-of-change protection is selected when the set value is
positive. When the frequency gradient protection is selected and the gradient exceeds
the set Start value df/dt value, the module reports the exceeding of the value to the
operate logic module.
Freq>/<
detection
Operate
logic
df/dt
detection
Blocking
logic
Section 4
Protection functions
OPERATE
OPR_OFRQ
OPR_UFRQ
OPR_FRG
START
ST_OFRQ
ST_UFRQ
ST_FRG
839