Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 5
Protection related functions
5.1.7
1064
I
1f
I
2f
Min operate current
GUID-434651E6-C694-4020-A6BF-649AB1A36193 V1 EN
Figure 571:
Inrush current in transformer
It is recommended to use the second harmonic and the waveform-
based inrush blocking from the transformer differential protection
function TR2PTDF if available.

Signals

Table 999:
INRPHAR Input signals
Name
Type
I3P
SIGNAL
BLOCK
BOOLEAN
Table 1000:
INRPHAR Output signals
Name
Type
BLK2H
BOOLEAN
Default
Description
-
Three-phase currents
0=False
Block input status
Description
Second harmonic based block
1MRS759142 C
REX640
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading