Signals; Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.6.2.7
4.6.2.8
Table 821:
LSHDPFRQ Group settings (Basic)
Parameter
Load shed mode
Restore mode
Start value Freq
Start value df/dt
Table continues on next page
856
Table 818:
Setting for a five-step restoring operation
Load-shedding steps
1
2
3
4
5

Signals

Table 819:
LSHDPFRQ Input signals
Name
U3P
BLOCK
BLK_REST
MAN_RESTORE
Table 820:
LSHDPFRQ Output signals
Name
OPERATE
OPR_FRQ
OPR_FRG
START
ST_FRQ
ST_FRG
RESTORE
ST_REST

Settings

Values (Range)
Unit
1=Freq<
6=Freq< OR df/dt
8=Freq< AND df/dt
1=Disabled
2=Auto
3=Manual
0.800...1.200
xFn
-0.2000...0.0050
xFn/s
Restore start Val setting
0.990 · Fn (49.5 Hz)
0.990 · Fn (49.5 Hz)
0.990 · Fn (49.5 Hz)
0.990 · Fn (49.5 Hz)
0.990 · Fn (49.5 Hz)
Type
Default
Description
SIGNAL
-
Three-phase voltages
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Block restore
BOOLEAN
0=False
Manual restore signal
Type
Description
BOOLEAN
Operation of load shedding
BOOLEAN
Operate signal for under frequency
BOOLEAN
Operate signal for high df/dt
BOOLEAN
Start
BOOLEAN
Pick-Up signal for under frequency detection
BOOLEAN
Pick-Up signal for high df/dt detection
BOOLEAN
Restore signal for load restoring purposes
BOOLEAN
Restore frequency attained and restore timer
started
Step
Default
1=Freq<
1=Disabled
0.001
0.975
0.0001
-0.010
1MRS759142 C
Restore delay time setting
200000 ms
160000 ms
100000 ms
50000 ms
10000 ms
Description
Set the operation mode for load shedding
function
Mode of operation of restore functionality
Frequency setting/start value
Setting of frequency gradient for df/dt
detection
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents