Section 4
Protection functions
562
CT ratio correction (B) = 300 A / 274.9 A = 1.091
CT connections
The connections of the primary current transformers are designated as "Type 1" and
"Type 2".
If the positive directions of the winding 1 and winding 2 protection relay currents
are opposite, the CT connection type setting parameter is "Type 1". The
connection examples of "Type 1" are as shown in the
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the CT connection type setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in the
The default value of the CT connection type setting is "Type 1".
Figure 309
and
Figure 311
and
Figure
312.
Technical Manual
1MRS759142 C
Figure
310.
REX640