1MRS759142 C
4.2.9.8
Table 565:
MFADPSDE Group settings (Basic)
Parameter
Values (Range)
Directional mode
Voltage start value
Operate delay time
Table 566:
MFADPSDE Group settings (Advanced)
Parameter
Values (Range)
Operating quantity
Min operate current
Tilt angle
Table 567:
MFADPSDE Non group settings (Basic)
Parameter
Values (Range)
Operation
Operation mode
Table 568:
MFADPSDE Non group settings (Advanced)
Parameter
Values (Range)
Peak counter limit
Start delay time
Reset delay time
Pol reversal
REX640
Technical Manual

Settings

Unit
2=Forward
3=Reverse
0.01...1.00
xUn
60...1200000
ms
Unit
1=Adaptive
2=Amplitude
3=Resistive
0.005...5.000
xIn
2.0...20.0
deg
Unit
1=on
5=off
1=Intermittent EF
2=Transient EF
3=General EF
4=Alarming EF
Unit
2...20
30...60000
ms
0...60000
ms
0=False
1=True
Step
Default
2=Forward
0.01
0.10
10
500
Step
Default
1=Adaptive
0.001
0.010
0.1
5.0
Step
Default
1=on
3=General EF
Step
Default
1
2
1
30
1
500
0=False
Section 4
Protection functions
Description
Directional mode
Voltage start value
Operate delay time
Description
Operating quantity selection
Minimum operate current
Characteristic tilt angle
Description
Operation Off / On
Operation criteria
Description
Peak counter limit for restriking EF
Start delay time
Reset delay time
Rotate polarizing quantity