Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.7.5
380
Table 424:
Analog signals
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off".
The operation of LOFLPTUC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
I_A
I_B
I3P
I_C
BLOCK
GUID-7BF39A6D-DAC5-43DF-8D35-26138AE01FBB V1 EN
Figure 209:
Functional module diagram
Level detector 1
This module compares the phase currents (RMS value) to the set Start value high
setting. If all the phase current values are less than the set Start value high value, the
loss of load condition is detected and an enable signal is sent to the timer. This signal
is disabled after one or several phase currents have exceeded the set Start value high
value of the element.
Level detector 2
This is a low-current detection module, which monitors the de-energized condition of
the motor. It compares the phase currents (RMS value) to the set Start value low
setting. If any of the phase current values is less than the set Start value low, a signal
is sent to block the operation of the timer.
Description
Three-phase currents
Timer
Level
t
detector 1
Level
detector 2
1MRS759142 C
OPERATE
START
Technical Manual