Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.17.3.6
Table 130:
UTVTR (3U) Non group settings (Basic)
Parameter
Voltage input type
Primary voltage
Secondary voltage
Division ratio
VT connection
Amplitude Corr A
Amplitude Corr B
Amplitude Corr C
Angle Corr A
Angle Corr B
Angle Corr C
Table 131:
UTVTR (3U) Non group settings (Advanced)
Parameter
Frequency adaptivity
192
Name
NPS_DR
PPS_DR
FREQ_DR

Settings

Values (Range)
Unit
1=Voltage trafo
3=Voltage sensor
0.100...440.000
kV
57...240
V
1000...20000
1=Wye
2=Delta
0.9000...1.1000
0.9000...1.1000
0.9000...1.1000
-20.0000...20.0000
deg
-20.0000...20.0000
deg
-20.0000...20.0000
deg
Values (Range)
Unit
0=Disable
1=Enable
2=Main frequency
source
3=Backup
frequency source
Type
Description
SIGNAL
Negative sequence current for disturbance
recorder
SIGNAL
Positive sequence current for disturbance recorder
SIGNAL
Measured frequency for disturbance recorder
Step
Default
1=Voltage trafo
0.001
20.000
1
100
1
10000
2=Delta
0.0001
1.0000
0.0001
1.0000
0.0001
1.0000
0.0001
0.0000
0.0001
0.0000
0.0001
0.0000
Step
Default
0=Disable
1MRS759142 C
Description
Type of the voltage input
Primary rated voltage
Secondary rated voltage
Voltage sensor division ratio
Voltage transducer measurement
connection
Phase A Voltage phasor magnitude
correction of an external voltage
transformer
Phase B Voltage phasor magnitude
correction of an external voltage
transformer
Phase C Voltage phasor magnitude
correction of an external voltage
transformer
Phase A Voltage phasor angle correction
of an external voltage transformer
Phase B Voltage phasor angle correction
of an external voltage transformer
Phase C Voltage phasor angle correction
of an external voltage transformer
Description
Frequency adaptivity selection
Technical Manual
REX640