1MRS759142 C
REX640
Technical Manual
Table 46:
SG operation mode = "Logic mode 2"
Input
BI_SG_2
BI_SG_3
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
any
any
any
any
Setting group 1 can be copied to any other or all groups from HMI (Copy group 1).
Test mode
The function has two outputs, BEH_TST and BEH_BLK, which are activated in test
mode according to
Table
Table 47:
Test mode
Test mode
Description
Normal mode
Normal operation
IED blocked
Protection works as in
"Normal mode" but the
ACT configuration can
be used to block
physical outputs to
process. Control
function commands are
blocked.
IED test
Protection works as in
"Normal mode" but
protection functions
work in parallel with test
parameters.
IED test and blocked
Protection works as in
"Normal mode" but
protection functions
work in parallel with the
test parameter. The
ACT configuration can
be used to block
physical outputs to
process. Control
function command is
blocked.
For more information, see the Test mode section in this manual.
BI_SG_4
BI_SG_5
FALSE
any
FALSE
any
FALSE
any
TRUE
FALSE
TRUE
TRUE
TRUE
any
47.
Protection
BEH_BLK
FALSE
TRUE
FALSE
TRUE
Section 3
Basic functions
BI_SG_6
Active group
any
1
any
2
any
3
FALSE
4
FALSE
5
TRUE
6
Protection
BEH_TST
FALSE
FALSE
TRUE
TRUE
121