1MRS759142 C
4.1.3.8
Table 392:
PHPVOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value low
Voltage high limit
Voltage low limit
Start value Mult
Time multiplier
Operating curve type
Operate delay time
Table 393:
PHPVOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
REX640
Technical Manual
Table 391:
PHPVOC Output signals
Name
OPERATE
START

Settings

Unit
0.05...5.00
xIn
0.05...1.00
xIn
0.01...1.00
xUn
0.01...1.00
xUn
0.8...10.0
0.05...15.00
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
40...200000
ms
Unit
1=Immediate
2=Def time reset
3=Inverse reset
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
0.05
0.01
0.05
0.01
1.00
0.01
1.00
0.1
1.0
0.01
1.00
15=IEC Def. Time
10
40
Step
Default
1=Immediate
Section 4
Protection functions
Description
Start value
Lower start value based on voltage control
Voltage high limit for voltage control
Voltage low limit for voltage control
Multiplier for scaling the start value
Time multiplier in IEC/ANSI IDMT curves
Selection of time delay curve type
Operate delay time
Description
Selection of reset curve type
357