Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.8.4.7
REX640
Technical Manual
In a power factor correction application, the ALARM and START outputs can be used
as controls to switch in capacitive loads when the Alarm value and Start value settings,
respectively, are exceeded. The ALARM output is set for a higher value to add the first
corrective load and the START output set for a second stage of corrective load, if
needed. The Start reset value and Alarm reset value settings allow their respective
outputs to remain activated to maintain the correction after power factor rises as a
result, but to drop out after it reaches a level where corrective capacitive loading is no
longer needed.
There are two general applications which can best utilize under power factor
protection; power-factor control and loss of excitation.
When applying the function for power-factor control, both the start value and the start
reset value should be the same sign (positive/negative) as well as the same direction
(leading/lagging). Additionally, the absolute value of the start reset value should be
greater than or equal to the absolute value of the start value. This allows the function
to properly control any power factor controls within the system.
When applying the function for loss of excitation, both the start value and the start
reset value should be the same sign (positive/negative), but the directions should be
different (leading/lagging). This application is well-suited to protect against back-
spinning. In this case the start reset value will only come into play once the system
provides power in the opposite quadrant of the start value, for example, lagging PF
turns to leading PF.

Signals

Table 918:
MPUPF Input signals
Name
Type
I3P
SIGNAL
U3P
SIGNAL
BLOCK
BOOLEAN
DISABLE
BOOLEAN
Table 919:
MPUPF Output signals
Name
Type
OPERATE
BOOLEAN
START
BOOLEAN
ALARM
BOOLEAN
Protection functions
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for activating the blocking mode
0=False
Signal to block the function during machine startup
Description
Operate
Start
Alarm
Section 4
981