1MRS759142 C
4.3.3.11
REX640
Technical Manual

Monitored data

Table 602:
TR3PTDF Monitored data
Name
Type
OPR_A
BOOLEAN
OPR_B
BOOLEAN
OPR_C
BOOLEAN
BLKD2H_A
BOOLEAN
BLKD2H_B
BOOLEAN
BLKD2H_C
BOOLEAN
BLKD5H_A
BOOLEAN
BLKD5H_B
BOOLEAN
BLKD5H_C
BOOLEAN
BLKDWAV_A
BOOLEAN
BLKDWAV_B
BOOLEAN
BLKDWAV_C
BOOLEAN
BLKD2HPHAR
BOOLEAN
BLKD2HPHAR_A
BOOLEAN
BLKD2HPHAR_B
BOOLEAN
BLKD2HPHAR_C
BOOLEAN
BLKD5HPHAR
BOOLEAN
BLKD5HPHAR_A
BOOLEAN
BLKD5HPHAR_B
BOOLEAN
BLKD5HPHAR_C
BOOLEAN
Table continues on next page
Protection functions
Values (Range)
Unit
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
Section 4
Description
Operate phase A
Operate phase B
Operate phase C
2nd harmonic restraint
block phase A status
2nd harmonic restraint
block phase B status
2nd harmonic restraint
block phase C status
5th harmonic restraint
block phase A status
5th harmonic restraint
block phase B status
5th harmonic restraint
block phase C status
Waveform blocking
phase A status
Waveform blocking
phase B status
Waveform blocking
phase C status
2nd harmonic restraint
blocking for PHAR LN,
combined
2nd harmonic restraint
blocking for PHAR LN,
phase A
2nd harmonic restraint
blocking for PHAR LN,
phase B
2nd harmonic restraint
blocking for PHAR LN,
phase C
5th harmonic restraint
blocking for PHAR LN,
combined
5th harmonic restraint
blocking for PHAR LN,
phase A
5th harmonic restraint
blocking for PHAR LN,
phase B
5th harmonic restraint
blocking for PHAR LN,
phase C