Goose Data Health T_Health; Function Block; Functionality; Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.19.4
3.19.4.1
3.19.4.2
3.19.4.3
202

GOOSE data health T_HEALTH

Function block

GUID-90EEEA26-B2B2-413E-8929-D53010D4E3A0 V1 EN
Figure 86:
Function block

Functionality

The GOOSE data health function T_HEALTH evaluates enumerated data of "Health"
data attribute. This function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs OK, WARNING and ALARM are extracted from the enumerated input
value. Only one of the outputs can be active at a time. In case the
GOOSERCV_ENUM function block does not receive the value from the sending
device or it is invalid, the default value (0) is used and the ALARM is activated in the
T_HEALTH function block.

Signals

Table 156:
T_HEALTH Input signals
Name
Type
IN
Any
Table 157:
T_HEALTH Output signals
Name
Type
OK
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
Default
Description
0
Input signal
Description
Output signal
Output signal
Output signal