ABB RELION REX640 Technical Manual page 565

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
GUID-15D8FF39-A3DC-4B80-855A-3F817C09CB78 V1 EN
Figure 305:
Inrush current detection logic
Differential calculation
The operating principle is to calculate on both ends differential current from currents
entering and leaving the protection zone by utilizing the digital communication
channels for data exchange. The differential currents are almost zero on normal
operation. The differential protection is phase segregated and the differential currents
are calculated separately on both ends.
RED 615
GUID-807098C6-1229-40A3-85F6-B7B02A9B3A2F V1 EN
Figure 306:
Basic protection principle
The differential current I∆ (I
formula:
I
I
I
=
LOC
+
REM
d
GUID-A758EAA5-2AE9-45B6-8295-F0C06B4B9B47 V1 EN
The stabilizing current I
the formula:
I
I
LOC
REM
I
=
b
2
GUID-D1649F99-80E4-4414-9516-1E1AAC7355A0 V1 EN
Depending on the location of the star points of the current transformers, the polarity
of the local end remote currents may be different causing malfunction of the
Communication
PROTECTED ZONE
) of the protection relay is obtained on both ends with the
d
(I
) of the protection relay is obtained on both ends with
bias
b
Section 4
Protection functions
RED 615
(Equation 88)
(Equation 89)
559