Section 3
Basic functions
3.25.1.4
Table 323:
RCHLCCH Settings
Parameter
Values (Range)
Redundant mode
Off
PRP
HSR
Filter Mode A_B
Off
SMV
GOOSE
GOOSE & SMV
Goose rate limiter
0.512...90.000
A_B
SMV rate limit A_B
0.512...90.000
Def. rate limit A_B
0.512...90.000
3.25.1.5
3.25.1.6
Table 324:
Diagnostic parameters for the redundant Ethernet channels LAN A and LAN B
Parameter
Values (Range)
Reset counters
FALSE
TRUE
GOOSE limit count
0...1000000
SMV limit count
0...1000000
Ucast limit count
0...1000000
Table continues on next page
296

Settings

Unit

Monitored data

Monitored data is available in four locations.
Monitoring/Communication/Ethernet/Activity/CHLIV_A
Monitoring/Communication/Ethernet/Activity/REDCHLIV_B
Monitoring/Communication/Ethernet/Link statuses/LNKLIV_A
Monitoring/Communication/Ethernet/Link statuses/REDLNKLIV_B

Diagnostics

Diagnostics data is available in Monitoring/Communication/Ethernet/
Diagnostics/A_B.
Unit
Step
Default
Off
10.000
70.000
8.000
Step
Default
FALSE
0
0
0
1MRS759142 C
Description
Mode selection for
Ethernet switch on
redundant
communication
modules. The
"None" mode is used
with normal and
Self-healing
Ethernet topologies.
Filtering selection for
message types
Goose rate limit
(Mbps)
Sampled measured
values rate limit
(Mbps)
Default rate limit
(Mbps)
Description
Reset counters
command
Goose rate limit
exceed count
Sampled measured
values limit exceed
count
Unicast rate limit
exceed count
REX640