REX640
Technical Manual
Steps to measure natural unbalance current
1.
The setting Natural Comp Enable must be set to "TRUE".
2.
The capacitor bank must be energized.
3.
The capacitor bank compensated unbalance current I_COM_AMPL is observed
from Monitored data.
4.
The command Record unbalance must be activated by selecting the value
"Record" which stores the unbalance reference for future unbalance calculations.
5.
The compensated unbalance current (I_COM_AMPL) is re-checked to be
approximately zero.
The natural unbalance recording should be made only during the
steady-state condition and when all the capacitor bank elements are
assumed to be in service.

Signals

Table 976:
HCUBPTOC Input signals
Name
I3P1
I3P2
BLOCK
Table 977:
HCUBPTOC Output signals
Name
OPERATE
START
ALARM
Settings
Unit
0.01...1.00
xIn
0.01...1.00
xIn
0.05...15.00
Type
Default
Description
SIGNAL
-
Three-phase currents 1
SIGNAL
-
Three-phase currents 2
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
Alarm
Step
Default
0.01
0.10
0.01
0.05
0.01
1.00
Section 4
Protection functions
Description
Start value
Alarm start value
Time multiplier in IEC/ANSI IDMT curves
1041