Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.20.16.5
Table 237:
Switching operation
Control input signals
SWITCH_TO
SWITCH_TO
2
3
FALSE
FALSE
TRUE
FALSE
TRUE
1)
x
1)
1)
x
x
1) No difference
254
There are a few special conditions which must be noted with the configuration.
Table 236:
Special conditions
Condition
U3P1/U3P2/U3P3/U3P4 connected to real
measurements
URES1/URES2/URES3/URES4 calculated

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off".
For this function, the setting is hidden and fixed to "on".
The switch logic depends on inputs SWITCH_TO2, SWITCH_TO3 and
SWITCH_TO4. Source 1 is selected as default and switching is done on increased
priority.
GRPOFF signal must be connected to unused voltage inputs. GRPOFF
signal is available as output from the Protection function block.
Outputs
SWITCH_TO
SOURCE1
4
FALSE
TRUE
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
If the numbers of channels connected to U3P1...U3P4 and
URES1...URES4 does not match with the number of connected
SWITCH_TOx inputs, the configuration of the function fails.
Outputs ALARM and URES_ALARM indicate bad quality data of system measurements
for selected U3P and URES, respectively.
Description
The function requires that at least one voltage
channel is connected.
The function requires that all three voltage
channels are connected to calculate the residual
voltage. Setting
that particular UTVTR.
SOURCE2
SOURCE3
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
FALSE
FALSE
VT connection must be "Wye" in
SOURCE4
Source for
U3P
FALSE
U3P1
FALSE
U3P2
FALSE
U3P3
TRUE
U3P4
Technical Manual
1MRS759142 C
Source for
URES
URES1
URES2
URES3
URES4
REX640