Characteristic
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
1) Positive-sequence voltage before fault = 0.0 × U
frequency injected from random phase angle
2) Measured with static signal output (SSO)
Negative-sequence overvoltage protection NSPTOV
Identification
Function description
Negative-sequence overvoltage
protection
Function block
GUID-5501CB0F-4646-462C-8547-B060621D0CF6 V1 EN
Figure 431:
Function block
Functionality
The negative-sequence overvoltage protection function NSPTOV is used to detect
negative sequence overvoltage conditions. NSPTOV is used for the protection of
machines.
The function starts when the negative sequence voltage exceeds the set limit.
NSPTOV operates with the definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
the definite timer or the function itself.
Analog channel configuration
NSPTOV has one analog group input which must be properly configured.
Table 745:
Analog inputs
Input
U3P
Protection functions
Value
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
, f
= 50 Hz, positive-sequence overvoltage of nominal
n
n
IEC 61850
IEC 60617
identification
identification
NSPTOV
U2>
Description
Three-phase voltages
Section 4
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
59NS