Section 5
Protection related functions
Table 1014:
CCBRBRF Non group settings (Advanced)
Parameter
CB fault delay
Measurement mode
Trip pulse time
Start latching mode
5.2.9
5.2.10
5.3
5.3.1
1078
Values (Range)
Unit
0...60000
ms
2=DFT
3=Peak-to-Peak
0...60000
ms
1=Rising edge
2=Level sensitive

Monitored data

Table 1015:
CCBRBRF Monitored data
Name
CCBRBRF
Technical data
Table 1016:
CCBRBRF Technical data
Characteristic
Operation accuracy
Operate time accuracy
Reset time
Retardation time
Master trip TRPPTRC
Identification
Function description
Master trip
Step
Default
10
5000
3=Peak-to-Peak
10
200
1=Rising edge
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current: f
±1.5% of the set value or ±0.002 × I
±1.0% of the set value or ±20 ms
Typically 40 ms
<20 ms
IEC 61850
identification
TRPPTRC
1MRS759142 C
Description
Circuit breaker faulty delay
Phase current measurement mode of
function
Pulse length of retrip and backup trip
outputs
Start reset delayed or immediately
Unit
Description
Status
±2 Hz
n
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
Master Trip
94/86
Technical Manual