Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 647:
MPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
CT connection type
CT ratio Cor Line
CT ratio Cor Neut
4.3.7.9
REX640
Technical Manual
Unit
1=on
5=off
1=Type 1
2=Type 2
0.40...4.00
0.40...4.00

Monitored data

Table 648:
MPDIF Monitored data
Name
OPR_A
OPR_B
OPR_C
INT_BLKD_A
INT_BLKD_B
INT_BLKD_C
ID_A
ID_B
ID_C
IB_A
IB_B
IB_C
I_ANGL_A1_B1
I_ANGL_B1_C1
I_ANGL_C1_A1
I_ANGL_A2_B2
I_ANGL_B2_C2
I_ANGL_C2_A2
Table continues on next page
Step
Default
1=on
1=Type 1
0.01
1.00
0.01
1.00
Type
Values (Range)
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
FLOAT32
0.00...80.00
FLOAT32
0.00...80.00
FLOAT32
0.00...80.00
FLOAT32
0.00...80.00
FLOAT32
0.00...80.00
FLOAT32
0.00...80.00
FLOAT32
-180.00...180.00
FLOAT32
-180.00...180.00
FLOAT32
-180.00...180.00
FLOAT32
-180.00...180.00
FLOAT32
-180.00...180.00
FLOAT32
-180.00...180.00
Section 4
Protection functions
Description
Operation Off / On
CT connection type. Determined by the
directions of the connected current
transformers
CT ratio correction, line side
CT ratio correction, neutral side
Unit
Description
Operate phase A
Operate phase B
Operate phase C
Internal block status
phase A
Internal block status
phase B
Internal block status
phase C
xIr
Differential current phase
A
xIr
Differential current phase
B
xIr
Differential current phase
C
xIr
Biasing current phase A
xIr
Biasing current phase B
xIr
Biasing current phase C
deg
Current phase angle
phase A to B, line side
deg
Current phase angle
phase B to C, line side
deg
Current phase angle
phase C to A, line side
deg
Current phase angle
phase A to B, neutral side
deg
Current phase angle
phase B to C, neutral side
deg
Current phase angle
phase C to A, neutral side
719