Section 4
Protection functions
4.12.5.9
4.12.5.10
1058

Monitored data

Table 996:
CNUPTOV Monitored data
Name
Type
START_DUR
FLOAT32
U_AMPL_RES
FLOAT32
U_ANGL_RES
FLOAT32
U_AMPL_N
FLOAT32
U_ANGL_N
FLOAT32
U_UNB_AMPL
FLOAT32
U_UNB_ANGL
FLOAT32
U_OPR
FLOAT32
CNUPTOV
Enum
Technical data
Table 997:
CNUPTOV Technical data
Characteristic
Operation accuracy
U
1)2)
Start time
value
Reset time
Reset ratio
Table continues on next page
Values (Range)
0.00...100.00
0.00...5.00
-180.00...180.00
0.00...5.00
-180.00...180.00
0.00...5.00
-180.00...180.00
0.00...5.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
voltage: f
±1.5% of the set value or ±0.002 × U
Start
= 1.1 × set
Typically 75 ms
Fault
Typically 40 ms
Typically 0.96
1MRS759142 C
Unit
Description
%
Ratio of start time /
operate time
xUn
Magnitude of capacitor
terminal open delta
voltage (either calculated
or derived)
deg
Angle of capacitor
terminal open delta
voltage (either calculated
or derived)
xUn
Magnitude of capacitor
neutral zero sequence
voltage
deg
Angle of capacitor neutral
zero sequence voltage
xUn
Magnitude of recorded
natural unbalance
compensation
component voltage
deg
Angle of recorded natural
unbalance compensation
component voltage
xUn
Calculated operating
voltage
Status
±2 Hz
n
Technical Manual
n
REX640