Monitored Data; Technical Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.9.9
4.1.9.10
402

Monitored data

Table 448:
MPTTR Monitored data
Name
Type
TEMP_AMB
FLOAT32
THERMLEV_ST
FLOAT32
THERMLEV_END
FLOAT32
T_ENARESTART
INT32
MPTTR
Enum
Therm-Lev:1
FLOAT32

Technical data

Table 449:
MPTTR Technical data
Characteristic
Operation accuracy
1)
Operate time accuracy
1) Overload current > 1.2 × Operate level temperature
Values (Range)
Unit
-99...999
°C
0.00...9.99
0.00...9.99
0...99999
s
1=on
2=blocked
3=test
4=test/blocked
5=off
0.00...9.99
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
Current measurement: ±1.5% of the set value or
±0.002 × I
(at currents in the range of 0.01...4.00
n
× I
)
n
±2.0% of the theoretical value or ±0.50 s
1MRS759142 C
Description
The ambient temperature
used in the calculation
Thermal level at
beginning of motor
startup
Thermal level at the end
of motor startup situation
Estimated time to reset of
block restart
Status
Thermal level of
protected object (1.00 is
the operate level)
REX640
Technical Manual