Analog Channel Configuration - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
3.9.3
REX640
Technical Manual
If some functions in the relay application are sensitive to start
frequently, it might be advisable to set the setting parameter Trig mode
to "From operate". Then only faults that cause an operate event trigger
a new fault recording.
The fault-related current, voltage, frequency, angle values, shot pointer and the active
setting group number are taken from the moment of the operate event, or from the
beginning of the fault if only a start event occurs during the fault. The maximum
current value collects the maximum fault currents during the fault. If frequency cannot
be measured, nominal frequency is used for frequency and zero for frequency gradient
and validity is set accordingly.
The measuring mode for phase current and residual current values can be selected with
the A measurement mode setting parameter.

Analog channel configuration

FLTFRC has twelve analog group inputs which must be properly configured.
Table 66:
Analog inputs
Input
1)
I3P1
1)
I3P2
1)
I3P3
1)
IRES1
1)
IRES2
1)
IRES3
1)
U3P1
1)
U3P2
1)
U3P3
1)
URES1
1)
URES2
1)
URES3
1) Can be connected to GRPOFF
See the preprocessing function blocks in this document for the
possible signal sources. The GRPOFF signal is available in the
function block called Protection.
There are a few special conditions which must be noted with the configuration.
Basic functions
Description
Three-phase currents
Three-phase currents
Three-phase currents
Residual current (measured or calculated)
Residual current (measured or calculated)
Residual current (measured or calculated)
Three-phase voltages
Three-phase voltages
Three-phase voltages
Residual voltage (measured or calculated)
Residual voltage (measured or calculated)
Residual voltage (measured or calculated)
Section 3
133