Section 4
Protection functions
4.12.3.5
1034
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The three-phase current unbalance protection for shunt capacitor banks operates on
the DFT measurement mode. The operation of HCUBPTOC can be described by
using a module diagram. All the modules in the diagram are explained in the next
sections.
I_A
I3P1
I_UNB_A
I_UNB_B
I3P2
I_UNB_C
BLOCK
GUID-9FDAE00A-E297-426D-96D1-B1E78DC4B16C V1 EN
Figure 557:
Function module diagram
Natural unbalance compensation
In the three-phase H-bridge-connected shunt capacitor bank configuration, the
unbalance currents I_UNB_A, I_UNB_B and I_UNB_C are measured at the
common points of the H-bridge.
Natural
Level
unbalance
compens-
detector 1
ation
Blocking
logic
Level
detector 2
1MRS759142 C
Timer 1
t
OPERATE
START
t
Timer 2
t
ALARM
REX640
Technical Manual