1MRS759142 C
4.2
4.2.1
4.2.1.1
4.2.1.2
4.2.1.3
4.2.1.4
REX640
Technical Manual
Earth-fault protection
Non-directional earth-fault protection EFxPTOC
Identification
Function description
Non-directional earth-fault protection,
low stage
Non-directional earth-fault protection,
high stage
Non-directional earth-fault protection,
instantaneous stage
Function block
GUID-82AD69E2-A313-4EDA-B666-86497DB366A6 V1 EN
Figure 219:
Function block
Functionality
The non-directional earth-fault protection function EFxPTOC is used as non-
directional earth-fault protection for feeders.
The function starts and operates when the residual current exceeds the set limit. The
operate time characteristic for low stage EFLPTOC and high stage EFHPTOC can be
selected to be either definite time (DT) or inverse definite minimum time (IDMT). The
instantaneous stage EFIPTOC always operates with the DT characteristic.
In the DT mode, the function operates after a predefined operate time and resets when
the fault current disappears. The IDMT mode provides current-dependent timer
characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself.
Analog channel configuration
EFxPTOC has one analog group input which must be properly configured.
Protection functions
IEC 61850
IEC 60617
identification
identification
EFLPTOC
Io>
EFHPTOC
Io>>
EFIPTOC
Io>>>
Section 4
ANSI/IEEE C37.2
device number
51G/51N-1
51G/51N-2
50G/50N
403