ABB RELION REX640 Technical Manual page 991

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
I_A
I_B
I3P
I_C
Io
IRES
OPR_MODE
REM_FLT_ARC
BLOCK
GUID-37CDAB96-E090-4843-812A-3D91EA30088C V2 EN
Figure 533:
Functional module diagram
Level detector 1
The measured phase currents are compared phasewise to the set Phase start value. If
the measured value exceeds the set Phase start value, the level detector reports the
exceeding of the value to Operation mode selector.
Level detector 2
The measured residual currents are compared to the set Ground start value. If the
measured value exceeds the set Ground start value, the level detector reports the
exceeding of the value to Operation mode selector.
ARC light detection
ARC detection information is received directly from the relay hardware input. The
detected ARC fault is directly signalled to the Operation mode selector and Fixed
delay 2 modules. There are four ARC detection inputs in the protection relay. Each
input is connected to a dedicated ARCSARC function.
Table 926:
ARC detection inputs connected to ARCSARC
ARC input
X11/ARC
X12/ARC
X13/ARC
X14/ARC
Operation mode selector
Depending on the Operation mode setting, Operation mode selector makes sure that
all required criteria are fulfilled for a reliable decision of an arc fault situation. The
operation is based on both current and light information in "Light+current" mode, on
light information only in "Light only" mode or on remotely controlled information in
"BI controlled" mode. When the "BI controlled" mode is in use and the OPR_MODE
Level
Operation
detector
mode
1
selector
Level
detector
2
ARC light
detection
ARC protection function
ARCSARC1
ARCSARC2
ARCSARC3
ARCSARC4
Section 4
Protection functions
Fixed delay 1
OPERATE
t
Fixed delay 2
ARC_FLT_DET
t
ALARM
Supervision
985