Clearing Of Record; Configuration - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.24.3.4
3.24.4
292
192 . 168 .
GUID-AE5B5039-1E75-4974-9153-6956F09B55B5 V1 EN
Figure 166:
Load profile record file naming

Clearing of record

The load profile record can be cleared with Reset load profile rec via HMI,
communication or the ACT input in PCM600. Clearing of the record is allowed only
on the engineer and administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters
are changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed, for
example, with ACT, the load profile recorder stops recording and previously collected
data are cleared.

Configuration

The load profile record can be configured with PCM600 or any tool supporting the
IEC 61850 standard.
The load profile record can be enabled or disabled with the Operation setting under the
Configuration/Load Profile Record menu.
Any demand output can be connected to any of the quantity channels of the load
profile record. The mapping is done in Application Configuration in PCM600.