Energy meter
Impulse ratio =
10 impulses/MWh
GUID-426F3489-F4A3-4498-9BBA-D97FA0757003 V1 EN
Figure 128:
Typical application of PCGAPC
PCGAPC can also be used as a general-purpose counter.
Hotline tag HLTGAPC
Identification
Function description
Hotline tag
Function block
GUID-BF2BEC0B-AB0C-4B60-A9A9-16E08073578F V1 EN
Figure 129:
Function block
Functionality
The hotline tag function HLTGAPC is used to block all reclosing of the breaker, from
both local and remote sources, when activated. When the function is activated locally,
it can only be reset locally. If activated remotely, it can be reset depending on the
Remote tag mode setting.
BI1
PCGGIO
PULSE_INPUT
VALUE_READ
READ_VALUE
COUNT_SAT
RESET
FREEZE_COUNT
Unit selection = Active Energy
Impulse ratio = 10
Impulse ratio prefix = Mega
IED
IEC 61850
IEC 60617
identification
identification
HLTGAPC
HLTGAPC
Section 3
Basic functions
Station HMI
Communication
channel
ANSI/IEEE C37.2
device number
HLTGAPC
249