Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.7.4.5
REX640
Technical Manual
Table 878:
Special conditions
Condition
U3P connected to real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "on" and "off".
The operation of UZPDIS can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
I_A
I_B
I3P
I_C
U_A_AB
U_B_BC
U3P
U_C_CA
BLOCK
GUID-7B1D9EC7-B134-4F40-B6FE-EC8FD29B4247 V1 EN
Figure 510:
Functional module diagram
Impedance calculation
This module calculates the impedance based on the selected voltages and currents.
The Impedance Meas mode and Phase Sel for Z Clc settings determine which voltages
and currents are to be used. If Impedance Meas mode is set to "1Phase-to-phase", the
Phase Sel for Z Clc setting is needed for determining which phase-phase voltages
("AB", "BC" and "CA") and currents should be used for calculating the impedance.
Description
The function can work with one voltage channel
connected (
"CA"), if the setting
to "1Phase-to-phase".
The function requires that all three voltage
channels are connected if
is set to "3Phase-to-phase".
Under
Impedance
impedance
calculation
detection
Blocking
logic
Section 4
Protection functions
Phase Sel for Z Clc set to "AB", "BC" or
Impedance Meas mode is set
Impedance Meas mode
Timer
OPERATE
t
START
943