All protocols are allowed for each network by default, and can be separately disabled.
Table 20:
Protocol control in the protection relay
Parameter
Configuration/Communication/
Protocols/Network1/FTP
Configuration/Communication/
Protocols/Network2/FTP
Configuration/Communication/
Protocols/HMI Port/FTP
Configuration/Communication/
Protocols/Network1/HTTPS
Configuration/Communication/
Protocols/Network2/HTTPS
Configuration/Communication/
Protocols/Network1/MMS
Configuration/Communication/
Protocols/Network2/MMS
Configuration/Communication/
Protocols/HMI Port/MMS
Configuration/Communication/
Protocols/Network1/DNP
Configuration/Communication/
Protocols/Network2/DNP
Configuration/Communication/
Protocols/Network1/Modbus
Configuration/Communication/
Protocols/Network2/Modbus

Protocol write access rights

Write access rights are configurable for FTP, MMS, and HTTPS protocols in
Configuration/Authorization. The write access parameters are used to narrow down
services that allow setting changes on different network interfaces. Disabling the FTP
and IEC 61850 MMS write access on Network 1 and 2 prevents the user from updating
the configuration to the protection relay from PCM600. Disabling the HTTPS write
access prevents the user from writing setting changes from WHMI.
Options
Off
On (Default)
Secure
Off
On (Default)
Secure
Off
On (Default)
Secure
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Off
On (Default)
Section 3
Basic functions
Description
Denies FTP and FTPS
Allows FTP and FTPS
Allows FTPS only
Denies FTP and FTPS
Allows FTP and FTPS
Allows FTPS only
Denies FTP and FTPS
Allows FTP and FTPS
Allows FTPS only
Denies HTTPS
Allows HTTPS
Denies HTTPS
Allows HTTPS
Denies IEC 61850 MMS
Allows IEC 61850 MMS
Denies IEC 61850 MMS
Allows IEC 61850 MMS
Denies IEC 61850 MMS
Allows IEC 61850 MMS
Denies DNP3
Allows DNP3
Denies DNP3
Allows DNP3
Denies Modbus
Allows Modbus
Denies Modbus
Allows Modbus