Section 3
Basic functions
3.2.4
3.2.5
3.2.5.1
86
Primary
IEEE 1588 v2
master clock
Managed HSR
Ethernet
switch
GUID-7C56BC1F-F1B2-4E74-AB8E-05001A88D53D V6 EN
Figure 11:
Example network topology with process bus, redundancy and IEEE
1588 v2 time synchronization

Secure communication

The protection relay supports secure communication for WHMI and file transfer
protocol using Transport Layer Security protocol. The WHMI must be connected
from a Web browser using the HTTPS protocol. File transfer client must use explicit
FTPS.

Communication services control

Ethernet ports

The protection relay allows the use of a secondary IP address for the station ports on
the communication modules COM1001...COM1003. This secondary IP network is
assigned to a single Ethernet port and can be used to make separate networks for
different communication protocols or, for example, a separate service network for
configuration purposes. Multicast station/bus communication, such as IEC 61850-9-2
LE sampled values and GOOSE, is only supported on the Network 1 interface. The
parameters for setting the secondary IP network are located under Configuration/
Communication/Ethernet/Network 2 address.
IEC 61850
HSR
Backup 1588
master clock
1MRS759142 C
Secondary
IEEE 1588 v2
master clock
(optional)
Managed HSR
Ethernet
switch
REX640
Technical Manual