ECC800 Data Center Controller
User Manual
Figure 5-13 Add alarm notification user information
Step 5 Click OK and the re-authentication page is displayed. Enter Login password and click
Submit.
----End
Follow-up Procedure
To modify or delete the email parameter settings, click Modify or Delete button, the
re-authentication page is displayed. Enter Login password and click Submit.
5.6 Commissioning the AC Actuator (Wireless
Networking)
If an AC actuator with wireless networking is configured, perform the following steps to set
its parameters.
Prerequisites
The upstream power input circuit breaker of the AC actuator is turned on.
Procedure
Step 1 Check and configure the wireless networking (802.15.4) function of the AC actuator.
Before networking, ensure that both the ECC800 and AC actuator have no network
parameters. That is, the RF_Z indicators on the ECC800 and AC actuator are both steady
green.
1.
Issue 02 (2019-02-28)
Select a notification level. If Warning is selected, then all alarms at the Warning level or higher will be
sent to the email address specified by Email address by email or to the phone number specified by
Mobile number by SMS.
If the RF_Z indicator on the ECC800 is not steady green, hold down the SW button on
the ECC800 for more than 6 seconds to make the ECC800 enter non-networking status.
If the RF_Z indicator on the AC actuator is not steady green, hold down the BLINK
button on the AC actuator for more than 10 seconds to make the AC actuator enter
non-networking status.
Hold down the SW button on the ECC800 main control module for 2 seconds (1.2–5
seconds allowed). The RF_Z indicator on the ECC800 main control modules turns from
Copyright © Huawei Technologies Co., Ltd.