Current Reversal And Weak-End Infeed Logic For Residual Overcurrent Rcrwpsch - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
5.13
5.13.1
5.13.2
5.13.3
5.13.4
REX640
Technical Manual
Current reversal and weak-end infeed logic for
residual overcurrent RCRWPSCH
Identification
Function description
Current reversal and weak-end infeed
logic for residual overcurrent
Function block
GUID-6D239C90-876C-4529-AAEE-504FC1BCFC05 V1 EN
Figure 634:
Function block
Functionality
The current reversal and weak-end infeed logic for residual overcurrent function
RCRWPSCH can be used when the communication logic for residual overcurrent
RESCPSCH requires additional logics to operate correctly in all power system
conditions.
In parallel feeder applications, the direction of the fault current on the healthy feeder
can change when the circuit breaker on the faulty feeder opens to clear the fault. This
can lead to an unwanted operation of the residual overcurrent protection on the healthy
parallel feeder when RESCPSCH with the permissive overreach scheme is used. The
main purpose of the current reversal logic is to prevent such unwanted operations.
The permissive communication schemes can operate only when the protection in the
remote terminal can detect the fault. This detection requires sufficient minimum fault
current. If such current is not available due to too weak a remote end source, the WEI
logic can be used to overcome the situation and trip the remote end breaker.
Analog channel configuration
RCRWPSCH has one analog group input which must be properly configured.
Protection related functions
IEC 61850
IEC 60617
identification
identification
RCRWPSCH
CLCRWN
Section 5
ANSI/IEEE C37.2
device number
85 67G/N
CREV,WEI
1177