Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 5
Protection related functions
5.10.6
1152
by the LCG output. The value of the LCG output is reset 200 ms after the CRG
signal reappears. The Loss of carrier time setting is set to "35" ms.

Signals

Table 1076:
DSOCPSCH Input signals
Name
Type
BLOCK
BOOLEAN
BLK_CS_OPR
BOOLEAN
CSBLK
BOOLEAN
CACC
BOOLEAN
CSOR
BOOLEAN
CSUR
BOOLEAN
CR_PRM
BOOLEAN
CR_BLOCKING
BOOLEAN
CR_INTER_TR
BOOLEAN
CRG
BOOLEAN
Table 1077:
DSOCPSCH Output signals
Name
Type
OPERATE
BOOLEAN
CS_PRM
BOOLEAN
CS_BLOCKING
BOOLEAN
CS_INTER_TR
BOOLEAN
CRL
BOOLEAN
LCG
BOOLEAN
Default
Description
0=False
Block signal for activating the blocking mode
0=False
Signal for blocking CS and Operate in all schemes
0=False
Reverse directed distance protection zone signal
for requesting activation of TxBlk
0=False
Permissive distance protection zone signal
0=False
Overreaching distance protection zone signal
0=False
Underreaching distance protection zone signal
0=False
Received teleprotection permissive from the other
side
0=False
Received teleprotection blocking from the other
side
0=False
Received direct trip from the other side
0=False
Carrier guard signal received
Description
Operate
Permissive transmitted to the other side
Blocking transmitted to the other side
Direct trip transmitted to the other side
Carrier received after unblock logic
Loss of guard
1MRS759142 C
REX640
Technical Manual