C.12.1 Configuring CIU 888
Part No.: 4417584_Rev12
Appendix C - Redundancy
C.12 Redundant CIU 888-Experion PKS Integration
Redundant CIU 888 and Experion PKS Integration requires necessary
configuration changes in CIU 888 using Service tool and in Experion
PKS using Quick Builder.
Perform the below steps for the required CIU 888 configuration using
CIU 888 Service tool:
1. On CIU 888 node, click FTE A port.
2. By default, the FTE tab appears displaying the Properties details.
3. Enter appropriate details in the IP address and Modbus port
number fields.
4. Select the Tranparency Mode and IP switch over decision maker
check boxes and click Apply.
5. Click Secondary FTE Host Port tab to view the Properties details.
6. Enter an appropriate IP address in the Secondary's IP address
field. (For example, if configured Primary CIU 888's IP address is
Configuration Manual
CIU 888